aquatherm red: sprinkler and fire protection piping system
The first plastic sprinkler piping system certified by VdS Schadenverhütung GmbH. Pipe and fittings are fused (socket fusion) into a homogeneous, leak-tight single piece with no gaskets or sealing elements. It can be cast directly into concrete for an invisible sprinkler installation.
- First VdS-certified plastic sprinkler pipe
- Fusion welded — no gaskets
- SDR 7.4, 25–125 mm
- Cast-in-concrete installation

In a wet system, corrosion is the weakest point of steel
aquatherm red MF HI: fusiolen PP-R FS. Flame-retardant, corrosion-resistant polypropylene developed for the specific requirements of sprinkler systems. For sprinkler / fire protection lines only; not suitable or approved for drinking water.
High corrosion resistance (none of the corrosion metal pipe suffers in contact with wet concrete)
Short installation time (fusion joint; e.g. 12 s welding time for 40 mm outside diameter)
Low weight compared with metal
Invisible fire protection (cast into concrete)
No sealing elements required
High impact resistance
Can be processed at temperatures below 0 °C
No waiting time after welding; the joint can be pressurised immediately
Colour: red body, 4 green stripes. Type code: MF = multilayer fibre-reinforced composite pipe; HI = hardly inflammable (building material class B1, flame retardant). Images and technical data: aquatherm GmbH (aquatherm.de, aquatherm red catalogue 7/2026). Values are as published by the manufacturer; the current catalogue governs project calculations.
SDR 7.4 pipe table
Catalogue pipe table; the support spacing and fire load columns for the same diameters are added from the catalogue.
| Outside dia. | Wall (mm) | Inside dia. (mm) | Water (l/m) | Weight (kg/m) | DN | Pack (m) | Support spacing (cm) | Fire load (kWh/m) |
|---|---|---|---|---|---|---|---|---|
| 25 mm | 3.5 | 18.0 | 0.254 | 0.249 | DN 15 | 116 | 140 | 2.69 |
| 32 mm | 4.4 | 23.2 | 0.423 | 0.400 | DN 20 | 58 | 160 | 4.32 |
| 40 mm | 5.5 | 29.0 | 0.660 | 0.621 | DN 25 | 58 | 180 | 6.73 |
| 50 mm | 6.9 | 36.2 | 1.029 | 0.968 | DN 32 | 29 | 205 | 10.48 |
| 63 mm | 8.6 | 45.8 | 1.647 | 1.521 | DN 40 | 17.4 | 230 | 16.46 |
| 75 mm | 10.3 | 54.4 | 2.323 | 2.165 | DN 50 | 17.4 | 245 | 23.42 |
| 90 mm | 12.3 | 65.4 | 3.358 | 3.101 | DN 65 | 11.6 | 260 | 33.55 |
| 110 mm | 15.1 | 79.8 | 4.999 | 4.642 | DN 80 | 5.8 | 290 | 50.19 |
| 125 mm | 17.1 | 90.8 | 6.472 | 5.974 | DN 90 | 5.8 | 320 | 64.63 |
Fire load: net calorific value of polypropylene Hu = 12.2 kWh/kg (DIN V 18230 T1) × pipe mass; combustion factor m = 0.8; fibre layers included. The product page and the catalogue pipe table give SDR 7.4; catalogue p. 12 also mentions SDR 11 and the Spanish DIT documents refer to an SDR 11 (S5) variant, for which the catalogue has no product table.


Source: aquatherm GmbH.
Certificates and standards
Only documents held in the aquatherm.de certificate archive are listed. Certificates apply under the legislation of the country concerned; acceptance by the project's fire consultant governs.
VdS approval
Plastic piping system for sprinkler systems; aquatherm red is the first plastic sprinkler piping system certified by VdS. The certificate PDF is a scanned image; details must be read from the document.
VdS approval number G4050042 (the number cited in the catalogue for the compensating joint)
Certificate PDF (14.10.2024)LPCB approval
Certificate No. 684a, Issue 04 — LPS 1260 Issue 3.1 (plastic pipes and fittings for use in automatic sprinkler systems). First issued 01.02.2006; Issue 04 dated 03.01.2019. The certificate annex lists a maximum working pressure of 12 bar for Red Pipe and fittings.
Certificate PDF (aquatherm.de)| Body | Country | Document | Date |
|---|---|---|---|
| IBS (Institut für Brandschutztechnik und Sicherheitsforschung) | Austria | — | 08-2013 (file name) |
| CNBOP-PIB | Poland | — | 08-2021 (file name) |
| VKF / AEAI | Switzerland | — | 12-2029, valid until (file name) |
| DIT (Instituto Eduardo Torroja) | Spain | DIT 526R-19 / 592R-19 (S3.2, SDR 7,4; sprinkler ve BIES), DIT 617R-19 / 618R-19 (S5, SDR 11; BIES ve sprinkler) | 25.11.2024 (file name) |
| SBSC | Sweden | Sertifika no. 14-430 | 07-2029, valid until (file name) |
| VNIIPO (All-Russian Research Institute for Fire Protection) | Russia | — | 03-2022 (file name) |
| SAI Global | Australia | SMKP20464.4 | 07-2030, valid until (file name) |
| AON | New Zealand | 4681/001 | 07-2013 (file name) |
| ZIK | Bosnia and Herzegovina | — | 07-2027, valid until (file name) |
| ZUS | Czech Republic | — | 2019 (file name) |
| SCC | Ukraine | — | 07.09.2026 (file name) |
| Belarus certificate | Belarus | — | 12-2022 (file name) |
FM Approvals or UL listing do not appear on the source pages or in the catalogue and are not claimed. DNV-GL, Lloyd's Register, Bureau Veritas, RINA, KRS, CRS and SRU type approvals are listed as documents common to green/blue/red (shipbuilding), not sprinkler approvals. Product page: further national or local certifications are in progress.
Catalogue pp. 16–17 "International Approvals" list Iceland, Spain, Germany (G4050042), Russia (VNIIPO), Poland, New Zealand, Austria, Australia, Hong Kong, Ukraine and the United Kingdom (LPS 1260 / LPCB 684a); the certificate-product assignment must be checked against the current document on aquatherm.de. No Turkish-specific certificate (TSE etc.) appears on aquatherm.de.
Application limits and design rules
| Topic | Rule |
|---|---|
| Inside suspended ceilings | 25–75 mm (DN15–DN50) as range and distribution pipe |
| Cast in concrete | 25–125 mm (DN15–DN90) as range and distribution pipe; fittings in the corresponding diameters |
| System type | Wet-system sprinkler installation; cast in concrete or in F30 ceiling zones. Also suitable for low-pressure fine spray technology (product page). |
| Design rule | For cast-in installation the aquatherm red technical catalogue and VdS CEA 4001 (sprinkler systems — planning and installation) apply. See CEA 4001 for deflector-to-ceiling distance. |
| Hydraulic calculation | Friction loss by the Hazen-Williams formula; C = 150 for sprinkler pipework and water supply calculations. |
| Test pressure | 10 bar (preliminary test 18 bar) |
| LPCB max. working pressure | 12 bar |
From the 'Approvals as line and distribution pipes' note in the catalogue pipe table. The approval document it belongs to is not stated; check the valid document for each country against the current certificate on aquatherm.de.
Fire protection requirements and standards for sprinkler systems vary locally. The use of aquatherm red must always be coordinated with the local or national fire protection authority, the contractor and the building insurer.
Suitability for dry-pipe systems and an operating temperature table for sprinkler lines are not given in the manufacturer's sources; written confirmation is obtained from the manufacturer per project. A general nominal working pressure or pressure-temperature table for the system is not published separately in the catalogue.
Cast-in-concrete installation
Pipe and PP fittings are cast into the concrete for a space-saving, invisible and corrosion-resistant sprinkler installation. The sprinkler outlet box (lower part, upper part, plug) is screwed to the formwork; after concreting the lower part is pulled and the sprinkler is connected directly to the thread.
- The pipe must be covered by at least 60 mm of concrete above and below.
- All sprinkler connections are fixed with cable ties and supported from below during the pour; the outlet box must be in the correct position and re-aligned and re-fixed if necessary.
- Pipe sections are fixed every 1.5–2 m (hangers or tie cord) to prevent sagging; the pipe must be fully embedded without voids.
- Concrete vibrators are used with care near the pipe; impact is avoided, especially below +5 °C.
- Open pipe ends and connections are closed before the pour.
- During the pour the pipe is kept pressurised at the permissible working pressure so that damage shows immediately. The gauge must read 0.1 bar and is fitted at the lowest point of the system.
Compensating joint: for correcting misaligned sprinkler connections in concrete ceilings (max. correction angle 12°) and compensating the distance between connection thread and sprinkler thread (max. 3 cm), with an adjustment tool. Max. working pressure 18 bar, tightening torque 29 Nm.
Fire compartmentation: any firestop system with a suitable approval can be used with aquatherm red. Solutions named in the catalogue: Rockwool Conlit 150 U pipe section (R30–R90 penetrations; with ROCKWOOL 800 / Teclit PS Cold), Flamro AWM II fire collar, Hilti. All boundary conditions of the abP/aBG documents apply.
Weld-in saddle
The main pipe wall is drilled with the aquatherm drill; the concave face of the welding tool goes into the hole and the saddle onto the heating sleeve. Because the saddle fuses with both the outer surface of the pipe and the inner wall of the hole, the joint is highly stable.

| Branch diameter | Drill / hole saw |
|---|---|
| 25 mm | Art. no. 9800050940 |
| 32 mm | Art. no. 9800050942 |
| 40 mm | Art. no. 9800050944 |
| 50 mm | Art. no. 9800050946 |
| 63 mm | Art. no. 9800050948 |
| 75 mm | Art. no. 9800050987 |
| 90 mm | Art. no. 9800050988 |
- The welding tool must have reached 260 °C; surfaces must be clean and dry.
- After 10 min of cooling the joint can take full load; the branch pipe is joined to the saddle socket by conventional socket fusion.
- The LPCB annex lists weld-in saddles in the range 40/20 … 125/63.
Socket fusion: steps and parameters
Heated-tool socket fusion (general rules of DVS 2207 Part 11 apply); DVS 2208 Part 1 for equipment and tools. Welding temperature 260 °C.
- 1
Cut the pipe square to the pipe axis; remove burrs and chips (aquatherm pipe shears or a suitable cutter).
- 2
Mark the welding depth on the pipe end with the template; mark the fitting position on pipe and/or fitting.
- 3
Push the pipe into the tool up to the welding depth mark without turning, and the fitting up to the stop. The heating time starts only when both parts are fully seated.
- 4
When the heating time has elapsed, remove the parts quickly from the tool and join them immediately without turning, until the mark is covered by the PP lip of the fitting.
- 5
No axial movement during the cooling time; incorrect pushing or positioning of the pipe causes joint defects.
- 6
75–125 mm pipes and fittings are welded only with welding device art. no. 9800050341 or machine art. no. 9800050148.
| Outside dia. | Welding depth (mm) | Heating (s) | Joining (s) | Cooling (min) |
|---|---|---|---|---|
| 25 mm | 16.0 | 7 | 4 | 2 |
| 32 mm | 18.0 | 8 | 6 | 4 |
| 40 mm | 20.5 | 12 | 6 | 4 |
| 50 mm | 23.5 | 18 | 6 | 4 |
| 63 mm | 27.5 | 24 | 8 | 6 |
| 75 mm | 30.0 | 30 | 8 | 8 |
| 90 mm | 33.0 | 40 | 8 | 8 |
| 110 mm | 37.0 | 50 | 10 | 8 |
| 125 mm | 40.0 | 60 | 10 | 8 |
Before welding, check the tool temperature with a fast-reading thermometer (aquatherm measuring device art. no. 9800050188) or the aquatherm thermo-colour pen (tolerance ±5 K; colour must change within 1–2 s). The first weld is made no earlier than 10 min after the welding temperature is reached (DVS 2207-11).
| Stage | Pressure | Duration | Rule |
|---|---|---|---|
| Preliminary test | 18 bar | 3 × 5 min | To let the pipe expand and relax; the system is depressurised between cycles. |
| Main test | 10 bar | 15 min | Immediately after the preliminary test; the test pressure may drop by at most 0.5 bar. |
| Final test | 10 bar | 60 min | Immediately after the main test without changing the pressure; the pressure read at the end of the main test may drop by at most 0.5 bar. |
The gauge must read a 0.1 bar change and is fitted at the lowest point of the installation. A hydraulic pressure test report is drawn up and signed by client and contractor with place and date; the aquatherm form is completed and sent to info@aquatherm.de. The 10-year warranty takes effect with this documented test.
Welding jig and machine
Electric welding jig for 63–125 mm; used in hard-to-reach places such as below ceilings or in narrow shafts. The clamping depth is marked at welding depth + 2 cm; the jaws are not released before the cooling time has elapsed; after heating the machine is backed off 3–7 mm to relieve jaw tension.
Prisma-light welding machine for 63–125 mm; the temperature lamp flashes at 260 °C; the heating time starts when pipe and fitting are fully seated in the tool.
Repair
The damaged section is cut out and welded like a new installation, or repaired with the pipe repair stick (art. no. 3090000012; tool art. no. 9800050307 / 9800050311).
Prefabrication
aquatherm red range and supply pipes required for a project can be prefabricated by aquatherm, reducing the number of welds on site. The leakage test is carried out in the factory and the pipes are delivered to site ready for installation.
Images and technical data: aquatherm GmbH (aquatherm.de, aquatherm red catalogue 7/2026). Values are as published by the manufacturer; the current catalogue governs project calculations.
Where is it used?
Fire protection, sprinkler systems, wall hydrant supply lines.
Public facilities
Wet-system sprinkler range and distribution pipes; cast into concrete or inside suspended ceilings.
Industrial buildings
Wet-system sprinkler range and distribution pipes; cast into concrete or inside suspended ceilings.
Healthcare
Wet-system sprinkler range and distribution pipes; cast into concrete or inside suspended ceilings.
Hotels
Wet-system sprinkler range and distribution pipes; cast into concrete or inside suspended ceilings.
Stadiums
Wet-system sprinkler range and distribution pipes; cast into concrete or inside suspended ceilings.
Residential
Wet-system sprinkler range and distribution pipes; cast into concrete or inside suspended ceilings.
Projects with aquatherm red

Kö-Bogen I and II
Sprinkler pipework cast directly into the floor slab; an invisible sprinkler solution in fair-faced concrete.

UN Campus
aquatherm red project featured in the catalogue reference section.
- KTM Motohall — Mattighofen, Austria. Invisible sprinkler system cast into fair-faced concrete; prefabricated elements sped up installation.
- Work-Life Centre, Gorch-Fock-Wall — Hamburg, Germany. Reference listed on the application page.
Images: aquatherm GmbH. These are the manufacturer's international references, not Kaskyapı installations.
Related products and services
aquatherm red — frequently asked questions
Where can aquatherm red be used?
Only in sprinkler / fire protection systems. It is not suitable or approved for drinking water.
How safe is aquatherm red?
Building material class B1 (DIN 4102-1) / B-s1,d0 (DIN EN 13501), flame retardant. No increased fire gas toxicity compared with natural materials; no dioxins are formed on combustion.
Which rules apply to plastic sprinkler lines?
Requirements vary locally; the application must be coordinated with the local fire protection authority, the contractor and the building insurer. In the United Kingdom the LPCB 'Technical Instruction aquatherm red pipe' (01/12/2012 Issue 2) applies.
Which firestop solutions can be used?
Any system with an equivalent approval; the catalogue names Rockwool Conlit 150 U, Flamro AWM II and Hilti solutions.
What should be observed in transport and storage?
Store flat and fully supported; avoid impact at very low temperatures; outdoors only in original packaging and for at most 6 months.
Does aquatherm red comply with Turkish fire regulations?
The Turkish Regulation on Fire Protection of Buildings and the approval of the project's fire consultant govern. No Turkish-specific certificate (TSE etc.) appears on aquatherm.de; the VdS (Germany) and LPCB (United Kingdom) certificates and ISO 9001/14001/50001 serve as reference. We share the approval documents with the quote.
Catalogue, certificates and forms
aquatherm GmbH publications in their original English; documents without a local copy open on aquatherm.de. Turkish summaries prepared by Kaskyapı are secondary; the original is the binding document.
- aquatherm red catalogue 7/2026PDF · 19.1 MB · external
- VdS certificate — aquatherm red pipe (14.10.2024)PDF · 1.7 MB
- Leakage test report formPDF · 0.2 MB · external
- All certificates (aquatherm.de)aquatherm.de · external
Images and technical data: aquatherm GmbH (aquatherm.de, aquatherm red catalogue 7/2026). Values are as published by the manufacturer; the current catalogue governs project calculations. Documents are the original files published by the manufacturer.